Ventilation solutions


Hatch Fans
In-line Duct Fans
Axial Fans
Centrifugal Fans
Smoke Extract Fans 400 ºC/2h - 300 ºC/2h
Pressurisation Systems for Staircases, Lobbies and Evacuation Routes
Explosive Atmospheres ATEX fans
Fans for Ovens
Fans for Industrial Applications
Roof Fans
EC Technology and Efficient Fans
Indoor Air Treatment Solutions
Ventilation for Houses
Air Curtains
Accessories

Smoke Extract Fans 400 ºC/2h - 300 ºC/2h


TCMP
400 ºC/2h centrifugal extractor fans, with forward curved impeller

400 ºC/2h centrifugal single inlet extractor fans for outdoor operation in fire risk zones.

Fan:
• Sheet steel casing.
• Forward curved impeller in galvanised sheet steel.
• Approved in accordance with standard EN 12101-3, with certificate no.: 0370-CPR- 0313.

Motor:
• Class F motors with ball bearings and IP55 protection.
• Motors with IE3 efficiency for powers equal to or greater than 0.75 kW, except single-phase, 2-speed and 8-pole.
• Three-phase 230/400 V 50 Hz (up to 4 kW) and 400/690 V 50 Hz (powers greater than 4 kW).
• Maximum temperature of air to be carried: S1 -25 ºC+ 250 ºC continuous service. S2 300 ºC/2h and 400 ºC/2h service.

Finish:
• Anti-corrosive finish in polyester resin, polymerised at 190 ºC, after degreasing with phosphate-free nanotechnology treatment.

On request:
• Fans with 2 speed motor.
• Belt driven extractor fans.